Guide · Testing a wallbox

Testing a wallbox: the guide for electricians

Measurements to DIN VDE 0100-600 (IEC 60364-6), inspection intervals under DGUV Regulation 3, function testing without a car and the test report – step by step.

Testing a wallbox: the short answer

A wallbox is tested before it is first put into service, after every repair and at regular intervals. The aim is to show that it is electrically safe and switches off in the event of a fault. A normal socket-outlet measurement is not enough: without a connected vehicle, the wallbox does not put voltage on the charging connector. You therefore need a test adapter or a wallbox tester that simulates an electric vehicle.

How to test a wallbox in 6 steps:

  • Visual inspection: check housing, charging cable, connector, supply line and labelling for damage.
  • Measure the protective conductor: continuity and low resistance of the protective conductor (RPE).
  • Measure insulation resistance: between the live conductors and to PE (RISO).
  • Check disconnection: loop impedance (ZS) and residual current device (RCD or DC residual current detection).
  • Check the function: simulate a vehicle, start charging, inject faults such as a protective-conductor interruption or a CP short circuit and check that the wallbox switches off.
  • Create the test report: document measured values, limits, result and tester.

Testing is a job for a qualified electrician. This guide explains each step, the applicable standards, sensible test intervals and how to choose the right tester. It follows the German and European rules (DIN VDE, DGUV); the international equivalents are named where they exist.

When must a wallbox be tested?

There are three occasions: initial verification before commissioning, periodic inspection at fixed intervals, and testing after modification or repair.

Initial verification. Every newly installed wallbox is tested to DIN VDE 0100-600 (international: IEC 60364-6) before handover: inspection, testing and measurement. Only with the test report is the installation handed over with documentation.

Periodic inspection. In a commercial setting in Germany, the wallbox is part of the fixed electrical installation. Under DGUV Regulation 3, § 5, the employer must have it tested at defined intervals. The employer sets these intervals so that the installation can be used safely until the next test (BetrSichV § 3 (6)). The implementation guidance to DGUV Regulation 3 gives reference values:

Item testedReference valueTesterBasis
Electrical installation and fixed equipment (wallbox, supply line)4 yearsQualified electricianDGUV Regulation 3, implementation guidance, table 1A
Residual current devices in fixed installations: press the test button6 monthsUserDGUV Regulation 3, implementation guidance, table 1A
Portable equipment (e.g. Mode 3 charging cable)per risk assessment; reference values by area of useQualified electricianDGUV Regulation 3, table 1B; test to DIN EN 50699 (VDE 0702):2021-06
Privately used wallboxno obligation under DGUV Regulation 3 (applies to businesses only)Qualified electricianRecommendation: follow the 4 years

The reference values apply to normal operating and ambient conditions. The electrician can set shorter intervals, for example for publicly accessible charge points with many users or in harsh environments. Manufacturers may specify different intervals for the RCD test button (DGUV, ETEM expert committee). The tables are reproduced in DGUV Information 203-050.

After modification or repair. After replacing components, changing the supply line or a fault, the wallbox is tested again. A test after major firmware updates is also sensible, because the charging behaviour can change.

Standards and regulations at a glance

Three sets of rules are central for wallbox testing: DIN VDE 0100-600 for initial verification, DIN VDE 0105-100 with DGUV Regulation 3 for periodic inspection, and IEC 61851-1 for charging behaviour.

Standard (edition)What it coversRelevant for
DIN VDE 0100-722:2019-06 (IEC 60364-7-722)Supply for electric vehicles: protective devices per connection point, residual current and overcurrent protectionPlanning, installation
DIN VDE 0100-600:2017-06 (IEC 60364-6)Verification of new installations: inspection, testing, measurementInitial verification
DIN VDE 0100-410:2018-10 (IEC 60364-4-41)Protection against electric shock, disconnection conditionsInstallation, measurement
DIN VDE 0105-100/A1:2017-06Operation of electrical installations, amendment A1: periodic inspectionsPeriodic inspection
DGUV Regulation 3Employer’s duty to have installations tested before commissioning and at intervalsCommercial wallboxes (Germany)
BetrSichV § 3Risk assessment, test intervals set by the employerCommercial wallboxes (Germany)
DIN EN IEC 61851-1 (VDE 0122-1):2019-12Conductive charging systems: requirements for the charging equipment, CP and PP signalsFunction test
DIN EN IEC 61557-1 (VDE 0413-1):2025-09Requirements for equipment testing and measuring protective measuresChoice of tester
DIN EN 50699 (VDE 0702):2021-06Periodic testing of electrical equipmentCharging cables
ISO 15118-2 / -20Digital communication between vehicle and charge point (PLC)Communication test
VDE-AR-N 4100Connection to the low-voltage grid in Germany; registration with the grid operator always, approval above 12 kVAInstallation

Each connection point needs its own residual current protection of at most 30 mA. Two solutions are permitted: an RCD type B, or an RCD type A or type F together with DC residual current monitoring (RDC-DD) to IEC 62955. An RCD type B is therefore not always mandatory. The responsible standards body confirms this in the DKE FAQ on DIN VDE 0100-722 (questions 1, 4 and 6).

The measurements step by step

The electrical safety test comprises six measurements, made on the grid side (supply line) and the vehicle side (charging connector). The vehicle-side measurements only work with an adapter or tester that simulates a vehicle.

MeasurementWhat is checkedPass ifBasisWith Easy Chester Micro
Visual inspectionDamage to housing, cable, connector; labelling; protective device matching the wallboxNo defectsDIN VDE 0100-600 (inspection)Photos in the test report (maintenance package)
Protective conductor resistance (RPE)Continuous, low-resistance protective conductorValue plausible for cable length and cross-sectionDIN VDE 0100-600Grid and vehicle side, test current 200 mA or 25 A
Insulation resistance (RISO)Insulation between live conductors and to PEAt least 1 MΩ at 500 V test voltage (table 6.1)DIN VDE 0100-600Grid and vehicle side, 250 / 500 / 750 / 1,000 V
Loop impedance (ZS)Disconnection of the fuse in the event of a faultDisconnection condition metDIN VDE 0100-410, -600Grid side
Residual current protection (tRCD)Tripping current and time of the RCD or DC residual current detectionWithin the limits of the RCD product standardDIN VDE 0100-600, DIN EN IEC 61851-16 / 30 / 100 / 300 mA, per phase L1–L3
Phase sequencePhase sequence on three-phase connectionCorrect phase sequenceDIN VDE 0100-600 (testing)Grid and vehicle side
Residual voltage (UOFF)Voltage at the connector after disconnectionBelow 30 V (AC) in less than 1 sVDE 0113-1Vehicle side

Device functions and standard references according to the Easy Chester Ultimate datasheet. The limits in the standard and the wallbox manufacturer’s data always prevail.

Grid side or vehicle side? On the grid side you test the installation up to the wallbox. On the vehicle side you test what reaches the charging connector, i.e. the protective measures through the wallbox. Only both sides together show whether a fault in the vehicle would be switched off safely.

Function test: testing a wallbox without a car

The function test shows whether the wallbox charges correctly and switches off reliably in the event of a fault. A real vehicle is unsuitable because it cannot create faults deliberately. A wallbox tester therefore simulates the vehicle via the CP signal (Control Pilot) and the PP resistor (Proximity Pilot) to IEC 61851-1.

Vehicle states to IEC 61851-1. The wallbox recognises the vehicle state from the voltage on the CP line:

StateMeaningCP voltage (nominal)
ANo vehicle connected+12 V
BVehicle connected, not charging+9 V
CVehicle charging+6 V
DVehicle charging and requesting ventilation (rarely used in practice)+3 V
EFault, e.g. short circuit CP–PE0 V
FCharging station not available−12 V

The nominal values apply with a tolerance. The charging station must keep them within ±0.7 V; the vehicle must accept values within ±1 V. A wallbox tester simulates the vehicle and therefore evaluates with ±1 V. It checks whether a vehicle would accept the value – this is not a conformance test of the charging station to the standard. Basis: DIN EN IEC 61851-1 (VDE 0122-1):2019-12, annex A (control pilot function).

Fault simulation. During an active charging session, typical faults are injected. The test is passed if the wallbox ends the charging session:

  • Interruption of the protective conductor (PE)
  • Short circuit on the CP line
  • Short circuit or interruption of the PP line – only for wallboxes with a charging socket-outlet (type 2, case B to DIN EN IEC 61851-1). There the wallbox uses the resistance between PP and PE to detect whether a charging cable is plugged in and which current it may carry (annex B).
  • Optional: insulation fault between one phase (L1, L2, L3) and PE with 2.5 kΩ, injected 5 seconds after charging starts

PP faults and tethered cables. If the wallbox has a permanently attached charging cable (case C), it does not need to evaluate the PP line: the PP contact in the connector is used by the vehicle. If such a wallbox continues charging during a PP fault, that is not a defect. With type 1 connectors to SAE J1772 (North America), the proximity contact with its latch switch mainly tells the vehicle that the connector is being released; whether a charging station also evaluates it depends on the device. In both cases the wallbox manufacturer’s data prevails.

Charging test. Finally, a real charging session runs. The tester measures voltage and current and shows the maximum charging power of the wallbox. This shows whether the configured charging current limit is correct.

More on testing without a vehicle: Testing a charging station without a real vehicle.

Which tester do I need to test a wallbox?

The choice depends on how many charge points you test and whether you only need to check the function or also prove electrical safety. There are three classes of device.

Device classWhat it can doWhat is missingSuitable for
Simulation plugSimulates vehicle states via CP and PP, shows whether the wallbox releases voltageNo safety measurements, no test reportQuick function check, fault finding
Test adapter + installation testerFull measurements to DIN VDE 0100-600 via the adapterTwo devices, fault simulation and charging test only partly, report often merged by handElectrical contractors with few wallbox tests
All-in-one wallbox testerSafety measurements on grid and vehicle side, fault simulation, charging test and communication in one sequence with one reportHigher purchase costService teams, operators and test service providers with many charge points

Easy Chester Micro as a wallbox tester. Easy Chester Micro from comemso belongs to the third class. It performs the safety tests on the grid and vehicle side: insulation resistance, protective conductor resistance, residual current protection, loop impedance, phase sequence and residual voltage. In addition there are fault simulation, charging test and communication testing to ISO 15118-2. The results go into a PDF test report rated PASS or FAIL.

If you also test DC charge points, choose Easy Chester Ultimate. It covers the same AC tests and adds CCS, CHAdeMO and NACS fast-charging points.

The test report

Without a report, a wallbox counts as untested. The report is the evidence for the operator, the accident insurer and the insurance company, and the basis for the next periodic inspection.

What belongs in it:

  • Occasion: initial verification, periodic inspection or test after repair
  • Operator, location and unique ID of the charge point
  • Manufacturer, type, serial number and firmware version of the wallbox
  • Type and rated current of the protective devices (fuse, RCD type)
  • Result of the visual inspection, defects found
  • All measured values with limit and assessment
  • Result of fault simulation and charging test
  • Tester used, with serial number and calibration date
  • Overall result, date, name and signature of the electrician
  • Date of the next test

Created automatically. Easy Chester Micro creates the report as a PDF with logo, address fields and comments. It contains the measured values with explanation, the communication steps, the maximum charging power and the MAC PLC address. The maintenance package adds the test location via GPS and photos of the visual inspection.

Checklist: a checklist for visual inspection, function test and measurements is included in our free guide to inspecting charging stations.

Common faults found in wallbox tests

Most defects are not in the wallbox itself but in the installation in front of it.

  • Wrong residual current protection: an RCD type A in front of a wallbox without DC residual current monitoring (RDC-DD). Only RCD type B or type A/F with RDC-DD are permitted.
  • No separate residual current protection per charge point: DIN VDE 0100-722 requires an RCD of at most 30 mA for each connection point. One shared RCD in front of several charge points is not enough.
  • Wrong phase sequence: on three-phase connections, a swapped phase sequence causes charging problems.
  • Voltage drop on long supply lines: common for parking spaces far from the distribution board.
  • Grid side only: without a vehicle-side measurement, it remains unknown whether the protective measures work at the charging connector.
  • No fault simulation: the wallbox charges, but does not switch off on a PE interruption or CP fault.

Basis for the first two points: DKE FAQ on DIN VDE 0100-722, questions 4 and 6.

What does a wallbox test cost?

The cost depends on whether you hire a service provider or test yourself. Service providers usually charge per charge point plus travel; with several charge points at one site, the price per point falls. Framework contracts for periodic inspections are common.

For electrical contractors and operators with many charge points, an own wallbox tester pays off. The time per test is decisive: a device that handles measurements, fault simulation and report in one sequence saves several steps compared with an adapter, an installation tester and a manual report.

Can I test my wallbox myself?

As a private person you may only press the RCD test button and check the wallbox for visible damage. Measurements on the installation are a job for a qualified electrician.

What you can do yourself:

  • Press the test button of the residual current device regularly. If it does not trip, inform your electrical contractor immediately.
  • Check the charging cable and connector for breaks, discolouration and scorch marks.
  • Watch for error messages in the wallbox app or status display.

Looking for a wallbox comparison before buying? Product tests by consumer and automotive magazines help there. This guide is for professionals who test an installed wallbox.

Outlook: testing communication to ISO 15118

In future, wallbox testing will also include digital communication. With the EU regulation AFIR, wired communication to ISO 15118 at AC charge points gains importance. It runs over power line communication (PLC) on the CP line.

The test checks whether the charge point establishes the PLC connection and runs through the communication sequence correctly. An important value is the attenuation from connection set-up to ISO 15118-3. Conspicuously high attenuation points to an impaired signal path.

Easy Chester Micro establishes communication to ISO 15118-2 with EIM authentication natively, without an external protocol converter. It documents the communication steps and the attenuation value in the test report. The extension to ISO 15118-20 is planned for Q1/2027. It does not replace a full AFIR conformance test; TLS-protected charging sessions are outside the scope of Micro.

Frequently asked questions about testing a wallbox

How do I test a wallbox?

Visual inspection, then measure protective conductor, insulation resistance, loop impedance and residual current protection. Then simulate a vehicle, inject faults, run a charging test and record everything in the test report.

Can I test a wallbox without a car?

Yes. A wallbox tester or test adapter simulates the vehicle via the CP and PP signals. Only then does the wallbox release voltage and can be measured on the vehicle side.

Which meter do I need to test a wallbox?

A simulation plug is enough for a pure function check. For testing to DIN VDE 0100-600 you need an installation tester with test adapter or an all-in-one wallbox tester such as Easy Chester Micro.

How often must a wallbox be tested?

The operator decides in the risk assessment. In Germany, DGUV Regulation 3 gives a reference value of 4 years for fixed installations and 6 months for the RCD test button. Shorter intervals make sense for public charge points or harsh environments. There is no obligation for private wallboxes.

Who may test a wallbox?

A qualified electrician with suitable measuring equipment. For commercial installations in Germany, the employer must also have appointed this person as qualified to carry out tests (TRBS 1203).

Does my wallbox need an RCD type B?

Not necessarily. Each charge point needs either an RCD type B or an RCD type A or type F together with DC residual current monitoring (RDC-DD), which is often already built into the wallbox.

What goes into a wallbox test report?

Occasion, charge point and device data, protective devices, visual inspection, all measured values with assessment, function test, tester used, overall result, inspector and next test date.

What is the difference between “testing a wallbox” and a “wallbox test”?

“Testing a wallbox” means the technical inspection of an installed wallbox. A “wallbox test” is usually a product comparison for buyers.